V/LNV SERIES 2018-04-28T08:45:15+00:00

V/LNV – Series

Suitable for firetube, watertube and cost iron boilers; the V series features a unique aerodynamic air damper design which permits accurate air-to-fuel settings for maximum combustion efficiency. The standard V series offers natural gas, propane gas, pressure atomized #2 oil and combination gas/oil fuel options at capacities from 1,300,000 to 16,800,000 Btu/hour. The low NOx V series offers natural gas, propane gas, pressure atomized #2 oil, and combination gas/oil fuel options at capacities from 1,300,000 to 14,700,000 Btu/hour. Through the use of advanced technology, the V series offers high turndown up to 10:1 on natural gas, and low emission capabilities with turndown up to 5:1.

Request a Quote

Features Include:

  • Natural gas, propane gas, pressure atomized #2 oil and combination gas/oil fuel options
  • Cam trim with 14-point adjustment range for consistent air/fuel ratios
  • Parallel positioning available for optimal control throughout the firing range
  • Up to 10:1 turndown on natural gas and optional low NOx with up to 5:1 turndown
  • Unique aerodynamic air damper design for optimal flow control
  • Forced draft for clean and efficient combustion
  • Top or rear mount panel options
  • Induced FGR
  • FGR modulating valve
  • FGR shutoff valve
  • Cam trim with 14-point adjustment range on FGR
  • No. 2 oil capability for back-up fuel
  • UL & cUL listed

Capacities and Specifications

V-Series Size 1

Burner Size 13 15 17 20 21 25 30 34
Frame Size 1 1 1 1 1 1 1 1
Gas Input (MBtu/hr) 1,300 1,500 1,700 2,000 2,100 2,500 3,000 3,400
Oil Input (U.S. gph) 9.3 10.7 12.1 14.3 15.0 17.9 21.4 24.3
Boiler HP @ 80% Eff. 31 36 40 48 50 60 71 81
Blower Motor HP 1 1/2 1/2 1/2 3/4 3/4 3/4 3/4 3/4
Blower Motor HP 2 3/4 3/4 3/4 1 1 1 1 1
Remote Oil Pump Motor HP 3 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2
Furnace Pressure ("w.c.) 0.4 0.5 0.7 0.9 1 1.2 1.4 1.8
Min. Gas Pressure (“w.c.) 5 8.6/ 9.2  4 11.4/ 11.7 4 14.3/ 14.7  4 19.7/ 20.2  4 21.5/ 22.1  4 9.6/ 10.4  4 8.7 10.3
Shipping Weight (lbs) 450 450 450 450 450 450 450 450

V-Series Size 2

Burner Size 35 40 42 45 50 54 55
Frame Size 2 2 2 2 2 2 2
Gas Input (Mbtu/hr) 3,500 4,000 4,200 4,500 5,000 5,400 5,500
Oil Input (U.S. gph) 25.0 28.6 30.0 32.1 35.7 38.6 39.3
Boiler HP @ 80% Eff. 83 95 100 107 119 129 131
Blower Motor HP  1 1 1 1 1/2 2 2 3 3
Blower Motor HP  2 1 1/2 1 1/2 2 2 3 3 3
Remote Oil Pump Motor HP  3 1/2 1/2 1/2 1/2 3/4 3/4 3/4
Furnace Pressure (“w.c) 1.9 1.2 1.3 1.4 1.8 2.1 2.2
Min. Gas Pressure (“w.c.)  5 8.1 10.4 11.5 10.8 13.6 19.2 19.7
Shipping Weight (lbs) 600 600 600 600 700 700 700

V-Series Size 3

Burner Size 60 63 70 80 84 90 100 105 110
Frame Size 3 3 3 3 3 3 3 3 3
Gas Input (Mbtu/hr) 6,000 6,300 7,000 8,000 8,400 9,000 10,000 10,500 11,000
Oil Input (U.S. gph) 42.9 45.0 50.0 57.1 60.0 64.3 71.4 75.0 78.6
Boiler HP @ 80% Eff. 143 150 167 190 200 214 238 250 262
Blower Motor HP 1 5 5 5 5 7 1/2 7 1/2 10 10 10
Blower Motor HP 2 - - - - - - - - -
Remote Oil Pump Motor HP 3 3/4 3/4 3/4 3/4 1 1 1 1/2 1 1/2 1 1/2
Furnace Pressure ("w.c.) 2.7 1.8 2.2 2.8 3.1 3.5 2.7 2.8 3
Min. Gas Pressure (“w.c.)  5 17.6 19.3 15.7 14.8 15.2 17.4 20.5 44.7 48.7
Shipping Weight (lbs) 700 700 700 700 700 800 800 800 800

V-Series Size 4

Burner Size 120 126 147 168
Frame Size 4 4 4 4
Gas Input (Mbtu/hr) 12,000 12,600 14,700 16,800
Oil Input (U.S. gph) 85.7 90.0 105.0 120.0
Boiler HP @ 80% Eff. 286 300 350 400
Blower Motor HP 1 15 15 15 15
Blower Motor HP 2 - - - -
Remote Oil Pump Motor HP 3 1 1/2 1 1/2 1 1/2 1 1/2
Furnace Pressure ("w.c.) 3.6 4.3 4.3 1.0
Min. Gas Pressure (“w.c.)  5 34.2 49.1 2.5 PSI 3.1 PSI
Shipping Weight (lbs) 1,450 1,450 1,450 1,450

LNV-Series Size 1

Burner Size 13 15 17 20 21 25
Frame Size 1 1 1 1 1 1
Gas Input (Mbtu/hr) 1,300 1,500 1,700 2,000 2,100 2,500
Oil Input (U.S. gph) 9.3 10.7 12.1 14.3 15.0 17.9
Boiler HP @ 80% Eff. 31 36 40 48 50 60
Blower Motor HP 3/4 3/4 3/4 3/4 3/4 3/4
Remote Oil Pump Motor HP 1/2 1/2 1/2 1/2 1/2 1/2
Furnace Pressure ("w.c.) 0.5 0.6 0.7 1 1.1 1.4
Min. Gas Pressure (“w.c.) 9.2 11.7 14.7 20.2 22.1 10.4
FGR Line Piping (in.) 4 4 4 4 4 4
Shipping Weight (lbs) 550 550 550 550 550 550

LNV-Series Size 2

Burner Size 30 34 35 40 42 45 50
Frame Size 2 2 2 2 2 2 2
Gas Input (Mbtu/hr) 3,000 3,400 3,500 4,000 4,200 4,500 5,000
Oil Input (U.S. gph) 21.4 24.3 25.0 28.6 30.0 32.1 35.7
Boiler HP @ 80% Eff. 71 81 83 95 100 107 119
Blower Motor HP 2 3 3 3 3 3 3
Remote Oil Pump Motor HP 3/4 3/4 3/4 3/4 3/4 3/4 3/4
Furnace Pressure ("w.c.) 1.5 1.9 2 1.4 1.5 1.6 2
Min. Gas Pressure (“w.c.) 8.7 10.3 8.1 10.4 11.5 10.8 13.6
FGR Line Piping (in.) 4 4 4 4 4 4 4
Shipping Weight (lbs) 600 600 700 700 700 700 700

LNV-Series Size 3

Burner Size 54 55 60 63 70 80 84 90
Frame Size 3 3 3 3 3 3 3 3
Gas Input (Mbtu/hr) 5,400 5,500 6,000 6,300 7,000 8,000 8,400 9,000
Oil Input (U.S. gph) 38.6 39.3 42.9 45.0 50.0 57.1 60.0 64.3
Boiler HP @ 80% Eff. 129 131 143 150 167 190 200 214
Blower Motor HP 5 5 5 5 7 1/2 7 1/2 7 1/2 10
Remote Oil Pump Motor HP 3/4 3/4 3/4 3/4 3/4 3/4 1 1
Furnace Pressure ("w.c.) 2.4 2.5 3 2 2.5 3.2 3.5 4
Min. Gas Pressure (“w.c.) 19.2 19.7 17.6 19.4 15.8 15.1 15.5 17.4
FGR Line Piping (in.) 4 4 4 4 4 4 4 4
Shipping Weight (lbs) 800 800 800 800 800 800 800 800

LNV-Series Size 4

Burner Size 100 105 110 120 126 147
Frame Size 4 4 4 4 4 4
Gas Input (Mbtu/hr) 10,000 10,500 11,000 12,000 12,600 14,700
Oil Input (U.S. gph) 71.4 75.0 78.6 85.7 90.0 105.0
Boiler HP @ 80% Eff. 238 250 262 286 300 350
Blower Motor HP 15 15 15 15 15 15
Remote Oil Pump Motor HP 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2
Furnace Pressure ("w.c.) 3.2 3.4 3.6 4.2 4.8 4.8
Min. Gas Pressure (“w.c.) 20.5 44.7 48.7 34.2 49.1 2.5 PSI
FGR Line Piping (in.) 6 6 6 6 6 6
Shipping Weight (lbs) 1,550 1,550 1,550 1,550 1,550 1,550

V/LNV Model

Gas Based
Model Fuel
VG Gas
LNVG Gas
Oil Based
Model Fuel
VL Oil
 
Gas/Oil Based
Model Fuel
VLG Gas/No. 2 Oil
LNVLG Gas/No. 2 Oil

Notes (V-Series):

  1. Motor ratings for gas only or gas/oil burners using a remote oil pump
  2. Motor ratings for oil only and gas/oil burners using a direct drive oil pump
  3. Remote oil pump is optional for frame size 1 and 2 but standard for frame sizes 3 and 4. All pump motors are 115/230/1
  4. Low/High and Full Modulation minimum gas pressure
  5. Lower gas supply pressure configurations available for New York City requirements
  • Input is based on fuel Btu content and altitude of 2,000 feet or less
  • If altitude >2,000 feet and <8,000 feet, derate capacity 4% per 1,000 feet over 2,000
  • Consult factory for higher altitudes
  • Gas input is based on natural gas with 1,000 Btu/cu.ft and 0.60 gravity
  • Oil input based on 140,000 Btu/gal.